Access Control DC Power Supply   Now Available!

Access Control Power Supply with fused output for 12 or 24VDC
View Enlargement


Hookup Diagram
Access Control Power Supply diagram
View Enlargement

Product Info Sheet


Installation Manuals
EAP-5D1
1 Output, 5A @ 12VDC, 4.5A @ 24VDC (field switchable)

Descriptions
The ENFORCER EAP-5D1 power supply is specifically designed for an access control system's electronic locks and accessories. The EAP-5D1 centralizes the power sources of access control equipment. It includes two supervision relays that can be used to integrate with other systems such as an alarm control panel. Robust fault response and indication also includes gradual shutdown on output overload as well as immediate shutdown on output short, signalled by flashing red LED and with auto-recovery once output short or overload is removed.

FEATURES
  • AC power failure supervision relay.
  • Battery failure supervision relay.
  • Selectable 2.2K-Ohm End-of-Line (EOL) resistor for AC failure and battery failure supervision relays via DIP switch.
  • Selectable delay timer (5 sec., 5 min., 5 hours) for AC failure supervision relay via DIP switch.
  • Board designed with overload and short-circuit protection, including automatic shutdown and LED overload indicator.
  • Over-current fuse-protected AC input.
  • Built-in back-up battery charger (back-up battery is optional).
  • Automatically switch to back-up battery if AC fails.
  • Individual AC input and DC output LED status indicators.
POWER
  • Field selectable for 12VDC or 24VDC output.
  • Operating voltage input 110~240 VAC.
  • Adjustable voltage range (11~15 VDC, 23~26 VDC) to compensate for voltage drop.
  • Supply current: 5 Amps @ 12VDC, 4.5 Amps @ 24VDC.
  • AC input fuse rating 3.15 Amps (glass fuse).

ENCLOSURE
  • Heavy-duty steel case to protect the power connections.
  • Removable steel cover for easy access.
  • Ventilation holes to prevent heat build-up.
  • Enclosure has enough room for two 7AH batteries.
  • 6-foot power cord and battery leads included.
  • Dimensions: 123/16" x 127/16" x 39/16".
  • Knock-out on the cover for optional cam lock.
Specifications
  Input Voltage 110~240VAC
  Output Voltage 12 or 24VDC selectable via DIP switch
  Adjustable Output
  Voltage Range
11~15 @ 12VDC setting, via VR switch
23~26 @ 24VDC setting, via VR switch
  No. of Outputs 1
  Supply Current 5A @ 12VDC / 4.5A @ 24VDC
  AC Input Fuse Rating 3.15A ( glass fuse )
  LED Status Indicator AC input ( Green ), DC Output ( Red )
  End-of-Line Resistor (EOL) Selectable ON ( 2.2K Ohm ) or OFF via DIP switch
  AC-Fail Relay Delay Timer   Selectable @ 5 sec., 5 min. or 5 hr. via DIP switch
  Supervision Relays Contact Rating: 3A @ 24VDC Dry Relay Output


Copyright 2008 by SECO-LARM U.S.A., Inc. All rights reserved. Modified: